The GoodWe BT series includes both high-voltage (HV) and low-voltage (LV) lithium battery modules. The BT series batteries connect to compatible GoodWe hybrid inverters and are monitored through the SEMS portal and SEMS app. They are sometimes paired with the GoodWe Lynx Home U inverter. LV (Low Voltage) BT modules operate at 48V nominal. HV modules operate at higher voltage strings. The wiring, isolation, and diagnostic approach differs between the two.
Checking Battery Status in SEMS
- Open the SEMS app or log in at semsportal.com
- Select your plant (installation)
- Navigate to the Energy Storage or Battery section
- Check:
- SOC (State of Charge): current percentage
- Battery Power: positive value = charging, negative value = discharging, zero = idle
- Any fault icons or warning banners
If the battery shows a fault icon in SEMS, note the fault description before proceeding.
Battery Not Charging During the Day
Check 1 — Working Mode
The most common cause of a battery not charging is an incorrect working mode:
- Self-Use Normal mode. Battery charges from solar surplus during the day, discharges in the evening. If the system is correctly wired and solar is producing, the battery should charge in this mode.
- Feed-in Priority The inverter prioritises grid export over battery charging. The battery only charges after the export target is met.
- Backup Only Battery does not charge from solar and does not power the home during normal operation. It is reserved entirely for grid outages.
- Off-grid Only for off-grid systems.
To check and change the working mode: SEMS app > Plant Settings > Working Mode. Set to Self-Use for normal daily charging operation.
Check 2 — Battery SOC Is Already at the Charge Ceiling
If the battery SOC is at 95% to 100%, charging has completed. The battery will appear idle or at zero charge rate. This is normal.
Check 3 — BMS Communication Fault
If SEMS shows a BMS communication fault, the inverter cannot communicate with the battery. The battery will not charge while this fault is active.
Power cycle procedure for GoodWe BT series:
- Open the SEMS app and note the current SOC (you will verify it has not changed after the restart)
- Turn off the AC isolator for the inverter at the switchboard
- Turn off the BT battery DC switch or the DC main disconnect on the battery module (the battery has its own power switch; consult the installation label on the battery for its location)
- Wait 5 full minutes
- Turn the battery DC switch back on
- Wait 30 seconds for the BMS to initialise
- Turn the AC isolator back on
- Wait 5 to 10 minutes for the inverter to restart fully
- Open SEMS and confirm the battery status has updated and the BMS fault has cleared
If the BMS communication fault returns after the power cycle: call AEU on 1300 996 917.
Check 4 — Temperature Below Minimum Operating Range
GoodWe BT lithium batteries have a minimum charging temperature of approximately 0 to 5°C. If the battery is installed in a location that drops below this in cold weather (uninsulated garage, external enclosure), the BMS will block charging as a cell protection measure.
The battery will discharge normally but will not accept a charge below the temperature threshold. Charging resumes once the battery temperature rises above the minimum.
If this is a recurring issue in winter: consider insulating the battery location or contacting AEU on 1300 996 917 to discuss options.
Battery Not Discharging in the Evening
Check 1 — Minimum SOC Floor
GoodWe hybrid inverters have a configurable minimum SOC floor (also called backup SOC or discharge floor). The battery will not discharge below this floor during normal operation. If the floor is set to 30%, the battery discharges to 30% SOC and stops.
Check this setting in SEMS under Plant Settings > Backup SOC (or similar label depending on the SEMS version).
If the floor is set higher than needed for your backup requirements, you can reduce it to allow more discharge each evening.
Check 2 — Working Mode Is Set to Backup Only
As described above: Backup Only mode prevents normal discharge. Set to Self-Use.
Check 3 — Time of Use (TOU) Conflict
If you have a TOU schedule configured in SEMS, the battery may be set to charge during a specific off-peak window and not discharge during certain hours. Review the TOU schedule in SEMS app > Plant Settings > Time of Use.
Common BT Battery Fault Codes in SEMS
BMS Alarm / BMS Communication Error: Most common. Follow the power cycle procedure above. If persistent: call AEU on 1300 996 917.
Overtemperature: The battery cells have exceeded the maximum safe temperature (typically 45 to 55°C). The battery stops charging and/or discharging. This may occur if the battery is in direct sunlight, in a very poorly ventilated space, or on an extreme heat day.
- Allow the battery to cool naturally
- Do not cover the battery or block ventilation
- If overtemperature occurs repeatedly on moderate-temperature days: call AEU on 1300 996 917.
Undervoltage / Cell Undervoltage: The battery SOC has dropped to or near 0%. The BMS has shut down the battery to prevent permanent cell damage. This can happen if the battery was fully discharged during an extended blackout.
- Restore AC power (grid power or confirm grid power is restored)
- The battery should automatically begin a slow recovery charge from the inverter
- If the battery does not recover within 2 to 4 hours of AC power being restored: call AEU on 1300 996 917.
Overvoltage: The battery voltage has exceeded the upper limit. This is uncommon with a correctly configured inverter but can indicate a failed charge control circuit. Call AEU on 1300 996 917.
Module Count Mismatch: For BT series installations with multiple modules in a stack, this fault indicates the inverter is detecting a different number of modules than expected. This typically indicates a loose module connection or a failed module. Call AEU on 1300 996 917.
Checking Without SEMS Access
If SEMS is offline, you can assess the battery by looking at the inverter display directly:
- The inverter display shows battery SOC and charge/discharge power
- LEDs or indicator lights on the battery module itself may show a fault (red) or normal (green) status
Consult the label on your battery module for the LED indicator meanings.
GoodWe BT Battery Warranty
GoodWe BT series batteries carry a 10-year product warranty in Australia. Warranted performance floor is typically 60% capacity retention at 10 years. Contact AEU on 1300 996 917 to initiate a warranty assessment if the battery capacity appears to have declined significantly.
When to Call AEU
Call AEU on 1300 996 917 if:
- BMS communication fault returns after a power cycle
- Overtemperature fault occurs repeatedly in moderate ambient conditions
- Undervoltage fault does not recover after grid power is restored
- Module count mismatch fault appears
- The battery SOC consistently shows 0% or an obviously wrong fixed value
- Battery capacity appears to have declined significantly compared to the first year of operation