A GoodWe battery that reaches full charge but does not discharge in the evening is almost always a working mode or settings issue, not a hardware fault.
Check 1 — Working Mode in SEMS
The most common cause. Open the SEMS+ app:
- Tap on your plant
- Tap the Settings icon (gear) or go to Device Settings
- Tap Work Mode
- Check what mode is set:
Self-Use (Self-Consumption) mode: Correct mode for daily cycling. The battery charges from solar during the day and discharges to the home at night automatically. If set to Self-Use and still not discharging: continue to Check 2.
Backup mode: The battery does not discharge in normal operation. It is reserved entirely for grid outages. All evening power comes from the grid. If set to Backup: change to Self-Use.
Feed-in Priority mode: Solar exports to the grid first. The battery charges from solar surplus and may reach full SOC, but may discharge only after grid export is maximised. If Feed-in Priority is set and you want evening discharge: consider switching to Self-Use.
Off-Grid mode: Only relevant for off-grid systems. Not applicable for normal grid-tied installations. If accidentally set to Off-Grid on a grid-connected system: change to Self-Use.
Check 2 — Minimum SOC (Backup Reserve) Setting
In Self-Use mode, GoodWe allows a minimum SOC (State of Charge) to be set as a backup reserve. The battery will not discharge below this reserve.
For example: if minimum SOC is set to 80%, the battery will only discharge from 100% down to 80% in the evening, then stop. The remaining 80% stays reserved.
To check:
- In SEMS Settings > Work Mode
- Look for Minimum SOC or Backup SOC setting
- If set to a high percentage (e.g. 80%): reduce it to 10 to 20% for maximum evening discharge, or to 0% if no backup reserve is desired
Check 3 — Time of Use Charging Schedule
If Time of Use (TOU) mode is active with a schedule that includes a charging period in the evening hours, the battery may be prevented from discharging during those hours.
Check the TOU schedule in SEMS Settings > Work Mode > Time of Use and confirm no evening charging period overlaps with when you expect the battery to discharge.
Check 4 — BMS Communication Fault
If the SEMS app shows a battery fault code or the battery SOC is not displaying correctly despite appearing charged:
Power cycle procedure:
- Turn off the AC circuit breaker for the GoodWe inverter at the switchboard
- Turn off the battery DC main switch (location varies by battery type: on GoodWe Lynx or ESA batteries, there is a main switch on the battery unit itself)
- Wait 5 minutes
- Turn battery DC switch back on and wait 30 seconds
- Turn AC circuit breaker back on
- Wait 5 to 10 minutes for restart
- Check SEMS for updated battery status
If battery communication fault persists after power cycle: call AEU on 1300 996 917.
Check 5 — Battery Temperature Too Low
GoodWe LV (low-voltage) and HV (high-voltage) batteries have a minimum discharge temperature. If the battery is located in an outdoor enclosure or unheated garage in winter and ambient temperature drops near or below 0°C, the BMS may block discharge.
Check the battery temperature in SEMS (battery detail page). If temperature is below 5°C: this is likely the cause. The battery resumes discharge once temperature rises.
What Correct Operation Looks Like in SEMS
In Self-Use mode with correct settings:
- Morning: battery SOC starts at minimum SOC level from overnight discharge
- During sunny day: battery SOC rises as solar surplus charges the battery
- After sunset: battery power flow shows negative (discharging) and home load is met by battery
- SOC falls through the evening as battery discharges
- SOC reaches minimum SOC threshold (typically 10 to 20%) and discharge stops for the night
- Grid makes up any remaining load after battery is at minimum SOC
If the power flow after sunset shows battery power as 0 or positive (charging from grid unexpectedly), and there is no TOU schedule directing this: work mode or minimum SOC setting is the most likely cause.
When to Call AEU
Call AEU on 1300 996 917 if:
- Working mode is correctly set to Self-Use and minimum SOC is set low (below 20%), but the battery still does not discharge
- A battery fault code appears in SEMS that does not clear after power cycle
- The battery temperature sensor appears stuck or is reading an unlikely value
- You cannot access the Work Mode settings in SEMS (some settings require installer-level credentials; AEU can adjust these remotely)