GoodWe ESA: Setting Backup SOC and Minimum SOC in SEMS+

Explains the difference between Backup SOC and Minimum SOC in GoodWe ESA systems, what each does, and how to set them in SEMS+ for your needs.

Battery Updated October 2026 4 min read
Quick answer

GoodWe ESA systems have two separate SOC settings that control how low the battery is allowed to discharge. Understanding the difference between them prevents unexpected behaviour. ---

Minimum SOC (Discharge Cutoff)

What it does: Sets the lowest SOC level the battery will discharge to during normal daily operation in General Mode or Battery First Mode. The battery stops discharging to the home when it reaches this level and the home switches to grid power.

Purpose: Protects the battery cells from deep discharge that can cause degradation. It also ensures the battery is not completely flat first thing in the morning before solar generation begins.

Recommended setting: 10 to 20% for most customers.

  • 10%: Maximum evening discharge. Battery supplies the home for as long as possible before switching to grid. Less reserve but maximum daily use.
  • 20%: A small buffer remains. If you have an unexpected overnight load spike the battery can cover a little more.
  • Above 20%: The battery stops discharging earlier in the evening. Only warranted if you want to ensure a reserve for some purpose.

How to set Minimum SOC:

  1. Log in to SEMS+ with owner access
  2. Go to Device Settings for your inverter
  3. Find Minimum SOC or Discharge Cutoff SOC
  4. Enter your preferred percentage
  5. Save

—

Backup SOC (EPS Reserve)

What it does: When operating in Backup Mode, the battery reserves this percentage of charge specifically for use during grid outages (EPS events). During normal grid-connected operation, the battery will not discharge below the Backup SOC level.

Purpose: Ensures that when the grid fails, the battery has a meaningful reserve available to power the home.

The interaction between Backup SOC and discharge:

In Backup Mode, the effective discharge cutoff is whichever is higher: the Minimum SOC or the Backup SOC.

Example: Minimum SOC set to 10%, Backup SOC set to 30%. In Backup Mode, the battery will discharge to 30% (not 10%) in the evening, holding the 30% in reserve for EPS. The home switches to grid at 30% SOC, not at 10%.

This means: A higher Backup SOC reduces the amount of battery capacity available for evening discharge but increases the reserve available for outages.

How to set Backup SOC:

  1. Log in to SEMS+ with owner access
  2. Go to Device Settings
  3. Confirm Working Mode is set to Backup Mode (or check for EPS/Backup settings if in other modes)
  4. Find Backup SOC or EPS Reserve
  5. Enter your preferred percentage (20 to 50% is typical)
  6. Save

—

Backup SOC has no effect unless backup wiring is installed

If your GoodWe ESA installation does not include a dedicated EPS backup circuit wired from the inverter’s EPS output, the Backup SOC setting is irrelevant. There is no backup capability to reserve charge for.

If you are unsure whether your installation includes backup wiring, call AEU on 1300 996 917.

—

Which mode should I use Minimum SOC vs Backup SOC in

ModeWhich setting controls discharge cutoff
General ModeMinimum SOC
Backup ModeBackup SOC (must be higher than Minimum SOC to take effect)
TOU ModeTarget SOC set within each TOU period
Feed-in PriorityMinimum SOC during discharge periods

—

My battery always seems to stop at 30% even though I set minimum SOC to 10%

If you are in Backup Mode and the battery consistently stops discharging at a higher level than your Minimum SOC setting, check the Backup SOC value. If Backup SOC is set to 30%, that overrides the 10% Minimum SOC setting while the system is in Backup Mode.

To allow the battery to discharge to 10%, either:

  • Lower the Backup SOC to 10% (this reduces your outage reserve)
  • Change to General Mode (no Backup SOC reservation applies)

—

The battery is going below the Minimum SOC I set

If the battery is discharging below your Minimum SOC setting:

  1. Confirm the setting was saved correctly in SEMS+ (refresh the settings page after saving to verify)
  2. If you are in TOU mode, the TOU period discharge minimum may be set lower than the Minimum SOC
  3. During EPS operation (blackout), the battery will discharge below the normal Minimum SOC because the EPS uses the Backup SOC as its floor (or the absolute minimum the BMS allows, typically 5 to 10%)
  4. If none of the above explain it, there may be a firmware or settings synchronisation issue. Call AEU.

—

Contact AEU

For help with SOC settings or to understand how these settings interact with your specific installation, call AEU on 1300 996 917.

Related articles

Did this fix it?

If the fault is still there, lodge a ticket with your system type, install date and any fault code showing. A technician will call you within one business day.

Lodge a ticket →
Free · No obligation

Planning a new energy upgrade?

Tell us your postcode and what you are considering. We will confirm which rebates your property qualifies for and what comes off the price — no cost, no obligation.

Takes about 60 seconds
Rebates come off the price up front
One team from design to commissioning
Or call 1300 996 917
Check my rebate eligibility

Talk to our team about your property and the rebates that apply.

Call 1300 996 917 Send an enquiry →