GoodWe ESA: Which Circuits Should Be on EPS Backup

How to decide which household circuits to connect to your GoodWe ESA EPS backup output, what the EPS power limit means for appliance selection, and what should never be connected to EPS.

Battery Updated October 2026 4 min read
Quick answer

The GoodWe ESA EPS (Emergency Power Supply) output is a separate circuit wired at the time of installation. It does not back up your entire home. It backs up only the specific circuits connected to the EPS output during installation. This is a deliberate design. Backing up your entire home would require much larger battery capacity and higher inverter power ratings than most residential systems have. The EPS approach lets you protect the most important loads with the capacity available.

EPS Power Limits

The EPS output has a maximum continuous power rating:

  • GoodWe EH series: approximately 3,000W continuous
  • GoodWe EHB series: approximately 5,000W continuous
  • GoodWe RS series: approximately 5,000W per phase
  • GoodWe ET series: approximately 5,000W per phase
  • GoodWe Omniverse: approximately 5,000W per phase

If the total load on the EPS output exceeds the limit, the EPS will shut down or trip. This is why appliance selection matters.

What Makes a Good EPS Circuit Candidate

Good candidates for EPS backup are loads that:

  • Are essential for safety, health, or daily function
  • Have modest power draw (well within the EPS limit when combined)
  • Run for extended periods (lighting, refrigeration) rather than short high-demand bursts
  • Cannot be deferred until grid power is restored

Practical examples of good EPS circuits:

  • Lighting circuits (LED lighting typically 5 to 20W per fitting)
  • Refrigerator and freezer (typically 100 to 400W combined during compressor cycle)
  • Modem and networking equipment (typically 20 to 50W)
  • Phone and device charging (50 to 150W)
  • Medical equipment (CPAP, nebuliser: 30 to 150W)
  • Security system and alarm panel
  • One television and set-top box (80 to 200W)

A typical combination of the above might draw 500 to 800W sustained, well within the EPS limit and giving many hours of battery backup.

What Should NOT Be Connected to EPS

The following should never be connected to the EPS output:

High-draw heating and cooling:

  • Split system air conditioners (typically 1,000 to 3,500W)
  • Electric space heaters (typically 1,000 to 2,400W)
  • Reverse cycle systems

These are the most common cause of EPS overload. During a power outage in summer or winter, the temptation to run air conditioning from the battery is understandable but likely to exceed the EPS limit and cause the system to trip.

High-draw kitchen appliances:

  • Electric oven or cooktop (typically 2,000 to 8,000W)
  • Microwave (typically 900 to 1,800W)
  • Kettle (typically 2,000 to 3,000W)
  • Toaster (typically 800 to 1,800W)

High-demand laundry:

  • Electric clothes dryer (typically 2,000 to 5,000W)
  • Washing machine (typically 500 to 2,500W depending on heating element)

Pool and garden:

  • Pool pump (typically 1,000 to 2,000W)
  • Pool heat pump
  • Bore pump or irrigation pump

EV charger:

  • A 7.4 kW EV charger draws more than twice the EPS limit. Never connect an EV charger to EPS.

The EPS Wiring Was Done at Installation

If your system has EPS capability and it was set up at installation, the EPS circuits were selected and wired at that time. You cannot add circuits to EPS without additional switchboard work by a licensed electrician.

If you are not sure which circuits are backed up: Turn off your main circuit breaker (or ask AEU) and see which items stay on. Those are your EPS-backed circuits.

If you want different or additional circuits added to EPS: Contact AEU on 1300 996 917. This requires a licensed electrician and switchboard modification.

EPS Does Not Mean Infinite Backup Time

Your battery capacity and the load on the EPS circuits determine how long backup lasts. Example:

  • 13.5 kWh battery at 80% SOC = 10.8 kWh available
  • EPS load of 600W sustained = approximately 18 hours
  • EPS load of 1,500W sustained = approximately 7 hours
  • EPS load of 2,500W sustained = approximately 4 hours

Your Backup SOC setting reserves a portion of the battery for EPS use. If Backup SOC is set to 20% and the battery is at 21% when the grid fails, only a small portion of the battery is available for the outage. See the Backup SOC settings article for how to configure this.

During a Power Outage on EPS

When the grid fails and EPS activates:

  • The switchover takes approximately 20 to 30 milliseconds
  • Some devices may momentarily reset (clocks, some electronics)
  • The inverter will show EPS mode on the display
  • SEMS+ will not update in real time if your modem/router is not on the EPS circuit
  • If the battery reaches Backup SOC, the EPS output will also shut down

Do not add additional loads to EPS-backed circuits during an outage that you would not normally have running. The EPS limit does not increase during an outage.

Related articles

Did this fix it?

If the fault is still there, lodge a ticket with your system type, install date and any fault code showing. A technician will call you within one business day.

Lodge a ticket →
Free · No obligation

Planning a new energy upgrade?

Tell us your postcode and what you are considering. We will confirm which rebates your property qualifies for and what comes off the price — no cost, no obligation.

Takes about 60 seconds
Rebates come off the price up front
One team from design to commissioning
Or call 1300 996 917
Check my rebate eligibility

Talk to our team about your property and the rebates that apply.

Call 1300 996 917 Send an enquiry →