The GoodWe ESA EPS (Emergency Power Supply) output is a separate circuit wired at the time of installation. It does not back up your entire home. It backs up only the specific circuits connected to the EPS output during installation. This is a deliberate design. Backing up your entire home would require much larger battery capacity and higher inverter power ratings than most residential systems have. The EPS approach lets you protect the most important loads with the capacity available.
EPS Power Limits
The EPS output has a maximum continuous power rating:
- GoodWe EH series: approximately 3,000W continuous
- GoodWe EHB series: approximately 5,000W continuous
- GoodWe RS series: approximately 5,000W per phase
- GoodWe ET series: approximately 5,000W per phase
- GoodWe Omniverse: approximately 5,000W per phase
If the total load on the EPS output exceeds the limit, the EPS will shut down or trip. This is why appliance selection matters.
What Makes a Good EPS Circuit Candidate
Good candidates for EPS backup are loads that:
- Are essential for safety, health, or daily function
- Have modest power draw (well within the EPS limit when combined)
- Run for extended periods (lighting, refrigeration) rather than short high-demand bursts
- Cannot be deferred until grid power is restored
Practical examples of good EPS circuits:
- Lighting circuits (LED lighting typically 5 to 20W per fitting)
- Refrigerator and freezer (typically 100 to 400W combined during compressor cycle)
- Modem and networking equipment (typically 20 to 50W)
- Phone and device charging (50 to 150W)
- Medical equipment (CPAP, nebuliser: 30 to 150W)
- Security system and alarm panel
- One television and set-top box (80 to 200W)
A typical combination of the above might draw 500 to 800W sustained, well within the EPS limit and giving many hours of battery backup.
What Should NOT Be Connected to EPS
The following should never be connected to the EPS output:
High-draw heating and cooling:
- Split system air conditioners (typically 1,000 to 3,500W)
- Electric space heaters (typically 1,000 to 2,400W)
- Reverse cycle systems
These are the most common cause of EPS overload. During a power outage in summer or winter, the temptation to run air conditioning from the battery is understandable but likely to exceed the EPS limit and cause the system to trip.
High-draw kitchen appliances:
- Electric oven or cooktop (typically 2,000 to 8,000W)
- Microwave (typically 900 to 1,800W)
- Kettle (typically 2,000 to 3,000W)
- Toaster (typically 800 to 1,800W)
High-demand laundry:
- Electric clothes dryer (typically 2,000 to 5,000W)
- Washing machine (typically 500 to 2,500W depending on heating element)
Pool and garden:
- Pool pump (typically 1,000 to 2,000W)
- Pool heat pump
- Bore pump or irrigation pump
EV charger:
- A 7.4 kW EV charger draws more than twice the EPS limit. Never connect an EV charger to EPS.
The EPS Wiring Was Done at Installation
If your system has EPS capability and it was set up at installation, the EPS circuits were selected and wired at that time. You cannot add circuits to EPS without additional switchboard work by a licensed electrician.
If you are not sure which circuits are backed up: Turn off your main circuit breaker (or ask AEU) and see which items stay on. Those are your EPS-backed circuits.
If you want different or additional circuits added to EPS: Contact AEU on 1300 996 917. This requires a licensed electrician and switchboard modification.
EPS Does Not Mean Infinite Backup Time
Your battery capacity and the load on the EPS circuits determine how long backup lasts. Example:
- 13.5 kWh battery at 80% SOC = 10.8 kWh available
- EPS load of 600W sustained = approximately 18 hours
- EPS load of 1,500W sustained = approximately 7 hours
- EPS load of 2,500W sustained = approximately 4 hours
Your Backup SOC setting reserves a portion of the battery for EPS use. If Backup SOC is set to 20% and the battery is at 21% when the grid fails, only a small portion of the battery is available for the outage. See the Backup SOC settings article for how to configure this.
During a Power Outage on EPS
When the grid fails and EPS activates:
- The switchover takes approximately 20 to 30 milliseconds
- Some devices may momentarily reset (clocks, some electronics)
- The inverter will show EPS mode on the display
- SEMS+ will not update in real time if your modem/router is not on the EPS circuit
- If the battery reaches Backup SOC, the EPS output will also shut down
Do not add additional loads to EPS-backed circuits during an outage that you would not normally have running. The EPS limit does not increase during an outage.