The pipe that has water dripping or flowing from it is called the discharge pipe or overflow pipe. It connects to the Temperature and Pressure Relief (TPR) valve on your hot water storage cylinder. The TPR valve is a mandatory safety device on all storage hot water systems (tanks). It is designed to open and release water if the pressure or temperature inside the tank exceeds safe limits. This prevents the tank from rupturing or exploding. The discharge pipe runs from the TPR valve to a safe point where released water can drain without scalding anyone (typically to a drain at ground level or to the outside of the building).
Why Is Water Coming Out of the Overflow Pipe?
There are three main reasons:
1. Normal Thermal Expansion (Small Amounts, Intermittently)
When a hot water system heats cold water, the water expands. In a closed system (where a pressure reducing valve or check valve prevents the expanded water from pushing back into the street main): this expansion raises the pressure inside the tank.
The TPR valve is designed to release a small amount of water when pressure peaks during heating. A small drip or brief trickle from the overflow during or just after a heating cycle can be normal in some installations, particularly where no expansion vessel is fitted.
If the dripping is small, brief (a few minutes), occurs only when the unit is heating, and then stops: this may be expansion discharge and may not be a fault. However, if it is happening at every heating cycle or the flow is significant: see the sections below.
2. High System Pressure (Pressure Reducing Valve Fault or Setting)
If the water supply pressure entering the hot water system is higher than the system’s rated pressure: the TPR valve may discharge more frequently or continuously.
The pressure reducing valve (PRV), also called a pressure limiting valve, is on the cold water supply to the hot water system. It limits incoming water pressure to a safe operating level (typically 500 to 600 kPa).
If the PRV:
- Is failing or has failed
- Is set to a pressure above the system's rated limit
- Has corroded and is no longer reducing pressure
The system pressure rises until the TPR valve opens to relieve it.
Signs: continuous or very frequent TPR discharge, higher than normal pressure at all taps in the home.
A PRV failure requires a licensed plumber. Call AEU on 1300 996 917.
3. Overtemperature (Thermostat or Boost Element Fault)
If the water temperature inside the tank rises above approximately 90 to 99°C (the thermal activation point of the TPR valve): the valve opens to release hot water and prevent dangerous steam pressure buildup.
Causes of overtemperature:
- Electric thermostat fault (element not turning off)
- Stuck heating element
- Heat pump controller fault causing continuous heating cycle
- Solar hot water system with no tempering or overtemperature management on very hot sunny days (no load on the tank)
Signs: TPR discharge is scalding hot, tank is very hot to touch, water at outlets is hotter than normal.
This is a more serious situation. Turn off the power and cold water supply to the hot water unit and call AEU on 1300 996 917.
4. Faulty or Ageing TPR Valve
TPR valves are designed to operate only under fault conditions. They are not designed for repeated cycling. Over time:
- The valve seat wears from repeated opening
- Mineral scale deposits can prevent the valve from sealing completely when it should close
- An older valve may weep continuously even when pressure and temperature are within normal range
This results in a constant small drip from the overflow pipe even when conditions are normal.
A continuously dripping TPR valve that is not related to a pressure or temperature fault needs to be replaced. This is a licensed plumber’s job. Call AEU on 1300 996 917.
Do not simply cap or block the overflow pipe. The TPR valve must remain able to discharge freely.
What to Do Now
Small intermittent drip during heating cycles: Monitor over one to two days. If it stops after heating completes and only happens briefly: this is likely thermal expansion. Mention it at your next service.
Continuous or large volume flow: Turn off the cold water supply to the hot water unit (the isolation tap on the cold water inlet pipe). This reduces the pressure and should reduce discharge. Call AEU on 1300 996 917 promptly.
Very hot water discharging and tank surface too hot to touch: Turn off the power to the unit (circuit breaker) AND the cold water supply. Call AEU on 1300 996 917 immediately.
Valve discharging frequently at every heating cycle: The PRV or valve itself likely needs attention. Call AEU on 1300 996 917.
Do Not Block the Overflow Pipe
The TPR valve discharge pipe must remain unobstructed and free to drain. Blocking, capping, or redirecting this pipe in a way that prevents discharge is a serious safety risk and does not comply with plumbing standards. If the TPR valve cannot discharge: the tank cannot relieve dangerous overpressure and overtemperature conditions.
When to Call AEU
Call AEU on 1300 996 917 if:
- Discharge from the overflow is continuous or large volume
- The water discharging is very hot (above 50°C at the discharge point)
- The tank surface or pipework is abnormally hot
- Discharge occurs at every heating cycle (not just an occasional small drip)
- The overflow pipe is already blocked or has been capped by someone else
- You are unsure whether what you are seeing is normal thermal expansion or a fault