GoodWe hybrid inverters are not silent. The following sounds are normal and expected:
Relay Clicks
You will hear distinct clicking sounds from the inverter:
- At sunrise when the inverter starts up (DC relays engaging)
- At sunset when the inverter shuts down
- When the inverter reconnects to the grid after a grid event (60-second reconnect click)
- When EPS mode activates or deactivates (grid relay switching)
These clicks are the internal contactors and relays operating. They are normal and indicate the inverter is working correctly.
Fan Noise
The inverter has a cooling fan. Fan noise varies:
- During moderate production: Fan may run slowly or not at all
- During high production (hot, sunny conditions): Fan runs faster and produces more noticeable airflow noise
- During EPS (battery backup) mode: Fan may run continuously
- At night: Fan typically does not run
Fan noise that increases on hot production days and decreases when production is lower is normal.
Electrical Hum
A low electrical hum from the inverter is normal. This is caused by the power electronics (inductors, transformers) vibrating at the switching frequency. It is normal and typically only audible in very quiet conditions or when standing close to the inverter.
Battery Electronics Sounds
The Lynx Home battery modules may produce:
- A very slight fan noise from the battery management cooling (if applicable)
- Occasional quiet relay clicks from the battery management controller switching
- A faint electronic hum from the BMS electronics
These are all normal.
Abnormal Sounds That Need Investigation
Loud Continuous Buzzing or Electrical Noise
A loud buzzing or electrical buzzing sound that is constant and louder than the normal hum:
This can indicate:
- Inverter electronics issue
- Loose internal component causing vibration
- Power quality issue (voltage or frequency instability)
Action: Turn off the AC isolator. If the loud buzzing stops, the issue is related to AC electrical operation. Call AEU on 1300 996 917.
Crackling or Arcing Sound
Any crackling, snapping, or arcing sound from the inverter, battery, or wiring is a serious warning sign.
Action: Turn off the DC isolator AND AC isolator immediately. Do not restart. Call AEU on 1300 996 917. If you smell burning or see discolouration, call 000.
Rattling or Metallic Vibration
Rattling that is rhythmic with inverter operation may indicate:
- A loose fan blade or fan mount
- A loose component inside the inverter
Action: Call AEU on 1300 996 917. A loose fan can cause overheating if it fails.
Fan Running Continuously at Maximum Speed
If the fan is running at maximum speed continuously even when production is low or during cool weather, this may indicate:
- Inverter overtemperature detection
- A fan control fault
Action: Check the inverter display for an F07 (overtemperature) code. Ensure the inverter location is not in direct sun and has adequate ventilation. If the display shows no fault but the fan is screaming: Call AEU on 1300 996 917.
Fan Squealing or Grinding
A squealing or grinding sound from the fan indicates the fan bearing is failing. A failed fan will cause the inverter to overheat.
Action: Call AEU on 1300 996 917. Fan replacement required.
Battery Module Sounds
For the Lynx Home F battery:
- Loud hissing or cracking from the battery enclosure: Turn off the battery via the management controller. Call AEU on 1300 996 917 immediately.
- Strong chemical smell from the battery: Turn off everything (battery first, then AC, then DC isolator). Ventilate the area. Call AEU on 1300 996 917 and if the smell is very strong or you feel unwell, call 000.
Battery fires, while very rare, are serious emergencies. Do not dismiss strong smells or unusual sounds from the battery enclosure.