Solar Victoria rebate round ends in 00d 00h 00m 00s Only 7 installer spots left this month

My Solar DC Isolator Keeps Tripping or Won’t Stay On — What Does This Mean?

Your solar DC isolator (the switch near or on the inverter) keeps turning itself off or won't stay in the ON position. Here is what DC isolators do, why they trip, and what it means.

Solar Updated October 2026 4 min read
Quick answer

The DC isolator is a rotary switch mounted on or very near the solar inverter. It is a mandatory safety device that allows the DC electricity coming from the solar panels to be disconnected from the inverter. It is labelled with ON/OFF or 1/0 positions, and is typically red, black, or yellow. DC isolators are required by Australian standards and must be within 3 metres of the solar inverter. Some inverters have the DC isolator built into the inverter housing.

Why a DC Isolator Might Trip or Not Hold

Cause 1 — DC Ground Fault / Insulation Fault

The most serious cause. If the inverter has detected a DC insulation fault (a breakdown in the insulation between the DC wiring and earth), the inverter may signal a fault condition that prompts the DC isolator to trip, or the inverter shuts down and cannot be restarted until the DC isolator is also switched off and back on.

On many inverters, an insulation/isolation fault code (GoodWe Fault 14, Fronius State 173, SolarEdge Error 7, Growatt Fault 10, Deye F12, Sungrow Isolation Fault) accompanies a DC isolator issue.

Action: Turn the DC isolator to OFF. Do not attempt to restart the system. Call AEU on 1300 996 917. A DC wiring inspection is required before the system can be re-energised. DC insulation faults are a fire and electric shock hazard.

Cause 2 — Worn or Failing DC Isolator

DC isolators are a known maintenance item in Australian solar installations. Early-generation DC isolators (particularly those installed before approximately 2014) have a history of failure due to:

  • Exposure to high DC voltage and current for many years
  • Heat cycling causing degradation of internal contacts
  • Water ingress into outdoor-mounted isolator housings
  • Arcing inside the switch body

A failing DC isolator may:

  • Feel hot to the touch during normal operation
  • Have visible discolouration or burn marks around the housing
  • Be difficult or stiff to turn
  • Emit a burning smell
  • Trip itself off or fail to hold the ON position

A failing DC isolator must be replaced. It is not safe to bypass it or hold it in place with a mechanical fastener. Call AEU on 1300 996 917.

Cause 3 — Overcurrent in DC Circuit

If the DC current from the solar array exceeds the rating of the DC isolator (or the DC wiring), an overcurrent protection device may trip. This should not occur during normal operation if the system was correctly installed. If it occurs regularly, there may be a wiring fault or a shading or temperature condition causing abnormal current. Call AEU on 1300 996 917.

Cause 4 — Moisture in the Isolator Housing

After heavy rain, moisture can enter an outdoor DC isolator housing. This can cause the isolator to trip when energised (the moisture provides a leakage path). Allow the isolator to dry thoroughly, then attempt to switch it back on. If it trips again on a dry day: the isolator housing seal has failed and water ingress will recur. Replace the DC isolator. Call AEU on 1300 996 917.

What to Do Right Now

If the DC isolator is currently off and the inverter is not running:

  1. Do not attempt to force the DC isolator into the ON position if it is difficult to turn or if it trips back off immediately.
  2. Check the inverter display for any fault code. Note the code if displayed.
  3. Check the inverter housing and DC isolator for any visible burn marks, discolouration, or burning smell.
  4. If any of the above are present: call AEU on 1300 996 917. Do not attempt to re-energise the system.
  5. If none of the above are present and this is the first time it has happened: attempt one power cycle (DC isolator off, AC breaker off, 5 minutes, AC breaker on, DC isolator on). If the system returns to normal: monitor closely.
  6. If the DC isolator trips again after a successful power cycle: call AEU on 1300 996 917.

Replacing an Old or Failing DC Isolator

Replacing a DC isolator is a job for a licensed electrician or solar technician. The replacement isolator must be rated for the DC voltage and current of the system. A standard 240V AC switch cannot be used for DC applications. Only DC-rated isolators designed for solar PV applications are suitable.

AEU can replace DC isolators. Call AEU on 1300 996 917.

When to Call AEU

Call AEU on 1300 996 917 if:

  • The DC isolator shows burn marks, discolouration, or a burning smell
  • The inverter shows an insulation or isolation fault code
  • The DC isolator trips repeatedly or will not hold the ON position
  • The DC isolator is hot to touch during normal operation
  • The solar system is more than 10 years old and the DC isolator has never been replaced (preventive replacement is recommended)
  • The DC isolator housing shows signs of moisture or water damage

Related articles

Did this fix it?

If the fault is still there, lodge a ticket with your system type, install date and any fault code showing. A technician will call you within one business day.

Lodge a ticket →
Free · No obligation

Planning a new energy upgrade?

Tell us your postcode and what you are considering. We will confirm which rebates your property qualifies for and what comes off the price — no cost, no obligation.

Takes about 60 seconds
Rebates come off the price up front
One team from design to commissioning
Or call 1300 996 917
Check my rebate eligibility

Talk to our team about your property and the rebates that apply.

Call 1300 996 917 Send an enquiry →